zuruck zur Themenseite

Articles and background information on the topic

Mains converter

Dr.-Ing. habil. Joachim Krause,

Grid stabilization and energy recovery

Switched, predominantly converter-fed devices such as electric drives generate harmonics and voltage drops. They also require reactive power. These grid perturbations interfere with other consumers across the entire power range and cause additional costs. Both control and harmonic reactive power contribute nothing to the active power, but are responsible for losses that have to be paid for.

Grid connection point A - principle G generator, XN grid reactance (transformer reactance, reactance of the grid choke), u generator voltage, u`ver voltage distorted by load at A, PC parallel capacitors, SK suction circuits (n = 5, 7...ordinal number of the harmonic; "red arrow" = reactive power; "blue arrow" = active power

The partial currents of all loads add up at grid connection point A. They cause voltage drops and asymmetries at the grid impedance. As a result, the feed-in voltage drops and is also distorted. Other consumers are disturbed, as drives, for example, generate particular grid perturbations due to their mostly fluctuating load and the associated switching processes.

Pulsed power converters eliminate or drastically reduce such problems. The supply voltage and current retain their sinusoidal shape and nominal amplitude, and their reactive power becomes adjustable. In addition, such four-quadrant converters improve the cost balance of the overall system. The aforementioned controllers complement conventional methods that are only dimensioned for a specific operating point (parallel capacitors, tuned suction circuits). At the same time, they can feed any braking energy released back into the grid (regenerative braking).

Use of electronics
It has been known for more than 40 years that force-commutated, self-commutated converters can compensate for grid perturbations and generate reactive power. However, this approach could only be implemented in a fully electronically controlled, economical and reliable manner with power electronic components (IGBT) and integrated circuits. Grid quality and security of supply increase for all consumers at slightly higher investment costs. Expenditure over the life cycle is reduced as installation, energy and maintenance costs decrease. Even during the investment phase, costs can be offset by lower costs for cables, filters, conventional compensation systems, transformers, buffer equipment and even by designing motors with a lower output.

Advertisement

Grid stabilizer
The active, fully electronic grid stabilizer or reactive power generator couples the supply grid with the load (capacitive as a reactive power converter for generating reactive power, DC consumers, machine/inverter of frequency converters for feeding AC machines). Its design corresponds to the pulsed inverter in a B6 bridge circuit.

The key features of the active, self-commutated forced-commutation mains converter (four-quadrant converter 4QS, Active Front End AFE) are:

  • in both directions (four-quadrant operation/controller, mains feedback in braking mode)
  • Current on the grid side (minimal grid feedback)
  • Inverter tilting in the event of grid failure in regenerative mode
  • Operation with a weak grid, compensation of grid voltage fluctuations or dips of up to approx. 60 percent, work as a step-up converter
  • Adjustment dynamics of current, voltage and phase shift
  • of reactive power (free, regulated power factor adjustment at the input)
  • with regard to commissioning, parameterization, operation and communication.

Digital control of the DC link voltage, shape and phase angle of the grid variables (harmonics, reactive power) is available for these tasks. All power converter and EMC standards are thus fulfilled.

Such a feed-in unit shields both the feeding grid and consumers from interference caused by problematic loads (inverters, non-linearities).

Application
The four-quadrant converter was first used in industry as a single-phase mains converter in ICE and Transrapid trains. The use as a pure reactive power converter favors the upper power range.

The application has become established as a mains converter for inverter-fed three-phase drives. It supplies the motor via a DC link and AC/machine converter. Predestined single-phase or three-phase applications for the controller include logistics and transportation equipment, wind turbines, test benches, fans, centrifuges and pumps, LV/MS motion drives, lifts/cranes and motion control.

For example, the ACTIVE FRONT END (AFE, http://www.siemens.de) feed-in/feed-back unit has the above-mentioned properties. Its mains current is practically sinusoidal,

The power factor cosϕ of the load can be set in the range 1 to 0.8 (capacitive or inductive) by direct parameterization or via a field bus as required. Alternatively, the reactive power can be regulated to the required level in order to cover the reactive power requirements of other loads independently of the power, i.e. to replace conventional compensation systems. Inverters often have an input filter that additionally reduces harmonics(http://www.abb.com).

Outlook
With the increase in the use of inverter-fed three-phase drives of all outputs (as well as other devices), grid perturbations are increasing. The necessary stabilization of grid conditions is not economically feasible through grid expansion, partly due to the increased cost pressure resulting from the liberalization of the energy markets. However, non-reactive converters are now even available to compensate for the reactive power of parallel consumers. In addition to savings on operating costs and/or capital expenditure, the drive equipped in this way ensures uninterrupted production and consistent quality even when the grid is weak.

  • Xing Icon
  • LinkedIn Icon
Advertisement
Back to topic page
Advertisement

You might also be interested in

Advertisement
Advertisement
Advertisement

Displacement measuring systems

Economic positioning

The integrated position measuring system IMS from Bosch Rexroth is now also available as IMS-compact for absolute measurement. The non-contact solution with magnetic measuring principle enables robust and economical position detection for linear...

read more...
Advertisement

Bosch Rexroth

Economic positioning

The integrated position measuring system IMS from Bosch Rexroth is now also available as IMS-compact for absolute measurement. The non-contact solution with magnetic measuring principle enables robust and economical position detection for linear...

read more...
Advertisement
Advertisement
Advertisement
Subscribe to our newsletter
Advertisement
Back to home